NGA-701
Addressable Input/Output Module
NGA-701 Addressable Input/ Output Module is a fully monitored device which permits the
interfacing of third party equipment with the Fire Alarm Control panel using normally open
dry contact connections while also providing a changeover output relay to control ancillary
equipment. The Green LED will pulse every time the unit is polled by the panel. The Yellow LED will be ON whenever there is a fault condition in the module and finally the Red LED will be ON
when there is an alarm condition at the module’s input.
The connection to the input is monitored for Fault (open or short circuit) and Alarm conditions. The
output relay can be powered from the detection loop (default) or optionally by an external 24 V DC
supply. Relay operation is confirmed by an onboard Yellow LED. The interface is used to monitor the
contacts of an external system which must be interfaced to the Fire Alarm System, for example a Flow
Switch in a sprinkler system to indicate if the sprinklers have been activated or extinguishant level
monitoring in Gas Extinguishing Systems etc.