NGA-707 is used as an interface between an NG-600 series conventional panels and any of Nortech
analogue addressable control panel. It allows the addressable panel to monitor and control the status of the conventional unit.
An 8 way DIL switch and a pluggable jumper are provided, which will be used for setting the module’s
address and the reporting mode. The module will transmit to the analogue addressable panel the
status of the NG-600 series Conventional Panels both in terms of Fire and Fault conditions and only one address
will be occupied per module. The module is reported by the addressable system as a Zone Monitoring
Unit. The unit is also equipped with 3 LEDS that will provide an optical indication of the module’s status,
namely: Polling Rate (GREEN), Faults (YELLOW) and Fire (RED).