NGA-IDB
Detector Base with Loop Isolator
NGA-IDB has been designed to provide protection against short circuit faults on Nortech
Addressable Fire Alarm system. The isolator protects the loop in the event of a short
circuit by disconnecting the section of the loop where the short circuit has occurred.
When the fault has been rectified, the isolating circuitry reconnects the affected part
of the System.
The Yellow LED is provided to indicate there is a short circuit in the loop. NGA-IDB is polarity sensitive
and can be damaged if connected with reverse polarity. Please be sure to note the polarity indicated
at the wiring terminals. Up to 32 devices may be fitted between each isolator (EN54) or 20 devices for
BS5839 compliance.